PR Electronics 2 Channel Galvanic Barrier, Pulse, ATEX, IECEx

Subtotaal (1 eenheid)*

€ 240,90

(excl. BTW)

€ 291,49

(incl. BTW)

Add to Basket
selecteer of typ hoeveelheid
Op voorraad
  • Plus verzending 5 stuk(s) vanaf 19 november 2026
  • Plus verzending 6 stuk(s) vanaf 24 november 2026
Heeft u meer nodig? Klik op 'Controleer leverdata' voor extra voorraad en levertijden.
Aantal stuks
Per stuk
1 +€ 240,90

*prijsindicatie

RS-stocknr.:
136-8697
Fabrikantnummer:
5202B1
Fabrikant:
PR Electronics
Zoek vergelijkbare producten door een of meer kenmerken te selecteren.
Alles selecteren

Merk

PR Electronics

Number of Channels

2

Product Type

Galvanic Barrier

Barrier Type

Galvanic Barrier

Mount Type

DIN Rail

Hazardous Area Certification

ATEX, IECEx

Terminal Type

Screw

IP Rating

IP20

Supply Voltage

21.6V ac, 253V ac, 19.2V ac, 300V ac

Signal Type

Pulse

Minimum Operating Temperature

-20°C

Maximum Safety Current

400mA

Maximum Safety Voltage

253V ac, 300V ac

Maximum Operating Temperature

60°C

Standards/Approvals

2014/35/EU, ATEX 2014/34/EU, EN 60947-5-6, EAC Ex TR-CU 012/2011, IEC 61140, 2014/30/EU, UL 508

Series

5200

Land van herkomst:
DK

PR Electronics 5202B Ex Pulse Isolator


PR Electronics 5202B pulse isolator for transmission of signals to the safe area from NAMUR sensors installed in hazardous areas. This signal conditioning isolator measures one or more pulse inputs and provides an identical number of isolated pulse outputs. The PR 5202B uses transformer and optical isolation techniques to provide 3.75 kVac galvanic isolation between the input, output and power terminals. The high level of electrical isolation means that input pulses sensed at the 5202B are not electrically connected to the output pulse. The 5202B has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.

Besides providing isolation, the PR 5202B is a barrier. This means that the module can make an intrinsically safe measurement of contacts and NAMUR sensors mounted in a zone 0/ Division 1 explosion hazard area. The PR 5202B limits the level of energy present at the contact or the NAMUR sensor to a low intrinsically safe level, thereby preventing ignition of a flammable atmosphere around the sensor – even if the sensor or the cable is damaged.

Features and Benefits


• 3.75 kVac galvanic isolation between input, output and supply

• One input signal can be used on two separate outputs

• A cable error alarm can be detected on a separate output

• Designed, developed and certified for use in SIL 2 applications

• Front LED indicates operation status and malfunction

• DIN rail mounting

PR Electronics - Ex Interfaces