PR Electronics 4500 Temperature Transmitter 300V, 70 °C, -25 °C
- RS-stocknr.:
- 175-6337
- Fabrikantnummer:
- 5437A2S
- Fabrikant:
- PR Electronics
Tijdelijk niet op voorraad
- RS-stocknr.:
- 175-6337
- Fabrikantnummer:
- 5437A2S
- Fabrikant:
- PR Electronics
Specificaties
Datasheets
Wetgeving en conformiteit
Productomschrijving
Zoek vergelijkbare producten door een of meer kenmerken te selecteren.
Alles selecteren | Attribuut | Waarde |
|---|---|---|
| Merk | PR Electronics | |
| Product Type | Temperature Transmitter | |
| Output Type | Relay | |
| Diameter | 44 mm | |
| Minimum Temperature Input | -200°C | |
| Maximum Temperature Input | 850°C | |
| Series | 4500 | |
| Depth | 20.2mm | |
| Maximum Supply Voltage | 300V | |
| Minimum Operating Temperature | -25°C | |
| Maximum Operating Temperature | 70°C | |
| Standards/Approvals | NE 43, NE 21 | |
| Hazardous Area Certification | EU RO marine, IECEx, DNV GL, UL, ATEX, Hardware Assessment, EAC, Zone 2, Zone, FM | |
| Alles selecteren | ||
|---|---|---|
Merk PR Electronics | ||
Product Type Temperature Transmitter | ||
Output Type Relay | ||
Diameter 44 mm | ||
Minimum Temperature Input -200°C | ||
Maximum Temperature Input 850°C | ||
Series 4500 | ||
Depth 20.2mm | ||
Maximum Supply Voltage 300V | ||
Minimum Operating Temperature -25°C | ||
Maximum Operating Temperature 70°C | ||
Standards/Approvals NE 43, NE 21 | ||
Hazardous Area Certification EU RO marine, IECEx, DNV GL, UL, ATEX, Hardware Assessment, EAC, Zone 2, Zone, FM | ||
- Land van herkomst:
- DK
5437A2S
The 5437A can be mounted in zone 2 and zone 22 / Class I, Division 1, Groups A, B, C, D.
5437 HART 7 Dual Input Temperature Transmitter
PR Electronics 5437 dual input temperature transmitter offers unrivalled performance in the most demanding of applications to convert a wide array of input types to a 4 – 20 mA output signal. The transmitter has 7 input terminals measuring one or two sensors, including two 4-wire RTDs, with individual sensor error detection. Configuring the transmitter with either HART 7 or HART 5 protocols provide flexibility and future proof communication.
Sensor Inputs
The PR 5437 provides unrivalled dual input versatility. Virtually any thermocouple or RTD plus linear resistance up to 100 kΩ, potentiometer, and bipolar mV signals. Input sensor redundancy function maintains process availability and safety by seamlessly switching to backup sensor in the event of primary sensor failure. An alert via HART can be used to allow scheduling of maintenance on the faulty sensor.
Installation Characteristics
Wiring - Innovative housing design means the 5437 temperature transmitter can be wired from either the inside or the outside of the terminals.
1/4 centre hole – A large diameter centre hole for easier installation over a wide range of probe mounting diameters.
Loop test pins - Accessible test pins allow measurement of loop current directly while maintaining loop integrity.
Status LED - On-board LED indicates faults according to NAMUR NE44 and NE107.
Jumper pins - Jumpers allow selection of write protection and transmitter burnout options.
Features and Benefits
• LED provides visual notification of sensor, transmitter, and loop status
• HART 7 and HART 5 communication protocols
• Sensor redundancy function switches to backup sensor in the event of sensor failure
• Sensor drift detection maintains measuring point reliability
• Flexible dual input capability, with choice of output modes
• Superior accuracy ensures true, reliable measurements
• Fast response time easily supports safety and cost-critical applications
• Very low temperature coefficient ensuring maximum accuracy across changing ambient conditions
• High galvanic isolation (2.5 kVAC / 55 VAC) providing protection from ground loops, high voltage transients and common mode interference
• Runtime meters provide a valuable history of the process temperature and the ambient temperature around the transmitter
Approvals
SIL Certification
Full third party functional safety assessment to SIL 2 / SIL 3. According to IEC 61508-2010 including firmware assessment to SIL 3. SIL enable/disable function to suit individual applications.
Full third party functional safety assessment to SIL 2 / SIL 3. According to IEC 61508-2010 including firmware assessment to SIL 3. SIL enable/disable function to suit individual applications.
Gerelateerde Links
- PR Electronics 5437 Temperature Transmitter Various Input, 7.5 → 48 V dc
- PR Electronics 5437 Temperature Transmitter Various Input, 7.5 → 30 V dc
- PR Electronics 5437 Temperature Transmitter Linear Resistance, Potentiometer, RTD, Thermocouple, Voltage Input, 7.5
- PR Electronics 6300 Temperature Transmitter, 8 → 35 V dc
- PR Electronics 3102 Temperature Transmitter Temperature Input, 16.8 → 31.2 V dc, -25 → +70 °C
- PR Electronics 3331 Temperature Transmitter Temperature Input, 5.5 → 35 V dc, -25 → +70 °C
- PR Electronics 3112 Temperature Transmitter Temperature Input, 16.8 → 31.2 V dc, -25 → +70 °C
- PR Electronics 3113 Temperature Transmitter Temperature Input, 16.8 → 31.2 V dc, -25 → +70 °C