PR Electronics 3 Series Signal Conditioner, Current Input, Current Output, 6 → 35V dc Supply, ATEX, IECEx
- RS-stocknr.:
- 136-8709
- Fabrikantnummer:
- 3186B1
- Fabrikant:
- PR Electronics
Subtotaal (1 eenheid)*
€ 136,65
(excl. BTW)
€ 165,35
(incl. BTW)
GRATIS bezorging voor bestellingen vanaf € 75,00
Op voorraad
- 11 stuk(s) klaar voor verzending vanaf een andere locatie
Heeft u meer nodig? Klik op 'Controleer leverdata' voor extra voorraad en levertijden.
Aantal stuks | Per stuk |
|---|---|
| 1 + | € 136,65 |
*prijsindicatie
- RS-stocknr.:
- 136-8709
- Fabrikantnummer:
- 3186B1
- Fabrikant:
- PR Electronics
Specificaties
Datasheets
Wetgeving en conformiteit
Productomschrijving
Zoek vergelijkbare producten door een of meer kenmerken te selecteren.
Alles selecteren | Attribuut | Waarde |
|---|---|---|
| Merk | PR Electronics | |
| Module Type | Signal Isolator | |
| Input Signal Type | Current | |
| Output Signal Type | Current | |
| Supply Voltage | 6 → 35V dc | |
| Hazardous Area Certification | ATEX, IECEx | |
| Operating Temperature Range | -25 → +70°C | |
| Series | 3 | |
| Minimum Operating Temperature | -25°C | |
| Maximum Operating Temperature | +70°C | |
| Alles selecteren | ||
|---|---|---|
Merk PR Electronics | ||
Module Type Signal Isolator | ||
Input Signal Type Current | ||
Output Signal Type Current | ||
Supply Voltage 6 → 35V dc | ||
Hazardous Area Certification ATEX, IECEx | ||
Operating Temperature Range -25 → +70°C | ||
Series 3 | ||
Minimum Operating Temperature -25°C | ||
Maximum Operating Temperature +70°C | ||
- Land van herkomst:
- DK
PR Electronics 3186 2-wire Transmitter Isolator
3186 type is a 1 or 2 channel input loop powered isolator. Inputs and outputs are floating and galvanically separated. The converter eliminates ground loops and can be used for measuring floating signals.
Features and Benefits
High basic 0.05% accuracy in all available signal ranges
2.5 kVAC isolation and have excellent noise immunity
NAMUR NE21 burst A criteria
Transmits rapid changes in process measurements to PLC/DCS for fast and accurate monitoring of critical signals
Low temperature coefficient better than 0.01% / °C in a wide -25 to +70°C ambient temperature range for precise measurements
Long term accuracy better than 0.1% / 3 years with no need for re-calibration
Installation in ATEX Ex zone 2 / IECEx Zone 2 / FM division 2
DIP-switch programming
Re-calibration is not needed after changing the DIP-switch range settings. Just change the DIP-switch, cycle the power to the unit and obtain the new, pre-calibrated I/O range. HART programming is enabled for selected devices.
Mounting
Devices can be mounted both vertically and horizontally with no air gap separation required. The devices snap onto a power rail or DIN rail and are easily detached by lifting the bottom lock.
High level of isolation
Safe galvanic isolation of 2.5 kVAC provides high noise immunity and prevents ground loops for accurate delivery of the process signal to your control system.
Device status indicators
A front LED indicates device status, e.g. an error in the set-up, sensor or hardware.
Over voltage- / polarity protection
All terminals can withstand up to ±31.2 VDC and are protected against incorrect supply wiring to ensure safe, error-free installation.
PR Electronics DIN Rail Mounting
Gerelateerde Links
- PR Electronics 3 Series Signal Conditioner, Current Input, Current Output, 6 → 35V dc Supply, ATEX, IECEx
- PR Electronics 3100 Series Signal Conditioner, Current Input, Current Output, 16.8 → 31.2V dc Supply, ATEX, IECEx
- PR Electronics 9200 Series Signal Conditioner, NPN, PNP Input, Relay Output, 19.2 → 31.2V dc Supply, ATEX, IECEx
- WAGO Signal Conditioner, Current Input, Current Output, ATEX, IECEx
- Phoenix Contact Signal Conditioner, Current Input, Current Output, ATEX, IECEx
- Weidmuller ACT20P Series Signal Conditioner, Current Input, Current Output, 20 → 30V dc Supply, ATEX, IECEx
- WAGO 857 Series Signal Conditioner, Current Input, Current, Voltage Output, 24V dc Supply, ATEX, IECEx
- WAGO JUMPFLEX Series Signal Conditioner, Current, Voltage Input, Current Output, 24V dc Supply, ATEX, IECEx