ABB 1SBL41 Contactor, 20V dc, 60 V dc Coil, 3-Pole, 75 A, 37 kW 20V dc, 60 V dc, 4 NO/1 NC, 690V

Subtotaal (1 eenheid)*

€ 435,16

(excl. BTW)

€ 526,54

(incl. BTW)

Add to Basket
selecteer of typ hoeveelheid
Informatie over voorraden is momenteel niet toegankelijk - Controleer het later nog eens opnieuw
Aantal stuks
Per stuk
1 +€ 435,16

*prijsindicatie

RS-stocknr.:
253-2042
Fabrikantnummer:
1SBL417001R7211
Fabrikant:
ABB
Zoek vergelijkbare producten door een of meer kenmerken te selecteren.
Alles selecteren

Merk

ABB

Coil Voltage

20, 60V dc

Product Type

Contactor

Number of Poles

3

Contact Voltage

690V

Contact Current

75A

Power Rating

37kW

Series

1SBL41

Function

Motor Control

Normal State Configuration

4 NO/1 NC

Auxiliary Contact Configuration

1 NO/1 NC

Number of Auxiliary Contacts

2

Terminal Type

Screw

Minimum Operating Temperature

-25°C

Operational Current Ie

72A

Control Circuit Voltage Uc

20, 60V dc

Contactor Application

Control Unit

Maximum Operating Temperature

55°C

Depth

108mm

Width

82mm

Standards/Approvals

CSA C22-2 N°14, EN 50155 (applicable parts), IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), IEC 61373, IEC/EN 60947-1, IEC/EN 60947-4-1, TR CU 001/2011 (on request), UL 508

Length

108mm

Pole and Throw Configuration

3P

ABB 1SBL41 Series Contactor, 75A Contact Current, 690V Contact Voltage - 1SBL417001R7211


This contactor is a three-pole switching device designed to control three-phase motors and heavy power circuits in industrial environments. It operates from a low-voltage DC control range and is intended for use where robust switching of high-voltage, high-current loads is required. The unit integrates auxiliary contacts and screw terminals for straightforward wiring in control panels and field installations.

Features and Benefits:


• 72A operational current supports continuous motor loads
• 75A contact rating for reliable switching capacity
• 690V contact voltage enables high-voltage circuit use
• 37kW power rating for substantial motor drive capability
• 20–60V DC Coil range offers flexible control voltages
• 1NO1NC auxiliary contacts permit straightforward interlocking

Applications


• Suitable for controlling 3-phase motor starters in factories
• Ideal for power distribution circuits in industrial plants
• Used with DC control systems in automation panels
• Can be used for retrofit railway traction equipment installations
• Suitable for use in rolling stock where shock and vibration standards apply

What Terminal arrangement does it use for field wiring?


Termination is via screw‑type connections for both power and auxiliary circuits, providing secure clamping for copper conductors.

What environmental temperatures can it tolerate during operation?


The device is specified to operate between -25°C and 55°C, covering typical indoor and some outdoor plant conditions.

How many poles are used for main power switching and what is their configuration?


Main power switching is carried out across three poles in a 3P configuration to manage three‑phase supplies.

What auxiliary contact arrangement is available for control logic integration?


It provides two auxiliary contacts arranged as one normally open and one normally closed to assist interlock and signalling functions.

Which standards apply to its use in rail and industrial contexts?


Relevant standards include approvals for electrical switching and selected railway and industrial applicable parts to address shock, vibration and safety requirements.